Part Number: ETI0001-1429
Model: ETI0001-N5A2-I/2.4
Rugged COTS
2400 VA Rackmount
UPS with Integrated Intelligent Power
Distribution Unit Combination
Navy
Standard N5 Configuration, PowerStation™
Isolated UPS, 2400 VA Rugged Rack Mount UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
Provides 20 Amps of UPS Output while Only Requiring 20 Amps Input
Maximizes the Amount for UPS Power Utilization from Existing Circuits

ETI0001-1429 Rugged COTS UPS Standard Front Panel Layout

ETI0001-1429 Rugged COTS UPS Standard Rear Panel Layout
The field proven Rugged Systems™ UPS line is ideally suited for military,
industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.
These units are equally suited for use in shipboard, airborne, vehicular, field
deployed or fixed locations with controlled or uncontrolled environments. The
"N5 Series" was specifically designed to save rack space and
installation costs while enhancing the functionality of both the UPS and PDU.
The "N5 Series" does not require a separate PDU since the PDU
functions are already integrated into the UPS module. This saves rack space,
cabling and expense while improving overall reliability.
The heavy duty
chassis occupy only 3U (5.25") of rack
space while delivering up to 2400 VA of clean, uninterruptible power. The rounded
metal corners and rugged handles, both front and rear, aid in safe handling. The optional
mounting kits include flanges that allow use of TAC-4 style shock isolation pins
and bushings used in some racks.
The internal shielded
input transformer provides galvanic isolation with provisions for domestic (115
VAC, CONUS) and optionally for international (230 VAC, OCONUS) input
voltages.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. This
unique circuit allows this UPS to deliver up to 20 amps to the load, while
utilizing less than 20 amps from the source, thus maximizing the use of existing
circuits.
The LED arrays
keep the operator informed as to the unit's status including load and battery levels. The
high intensity audible alarm can be heard in high noise environments, yet is easily
adjustable to suit quieter conditions. All controls and protective devices are brought to
the front and rear panels with critical switches or breakers guarded. Further, all front panel
devices are recessed to prevent damage or accidental operation. Various
optional power distribution controls are available which mount on the front panel or
remotely.
The internal intelligent PDU allows control of
the individual output circuits incorporating thermal and interlock interfaces
for additional control and safety, plus Battleshort override. The display and control panel can be mounted remotely in the rack or on the
front panel with only a logic level cable connection. The input
circuit breaker and the galvanic isolation transformer
all provide a double pole isolated source for all installations including shipboard systems or
overseas locations where phase references and grounding are not consistent.
The rear panel provides locking connectors for the input and output power. Multiple
input and output power panel options are available. A removable and washable intake air filter and high
capacity stainless steel ball bearing fan provide added protection in both controlled and hostile
environments. The air is drawn from the rear and exhaust air is diverted out the front vent, with alternate
air flow directions optional. The external battery connector allows the safe and easy addition of
the standard or extra battery modules without having to shut the unit down.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the
Battery
Technology section. A
frequency selection switch is available for those sites requiring 50 hertz output instead
of the standard 60 hertz. The Status connector provides an interface with
optional computer software providing loss of AC and low battery status as well as remote shut down
capability.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N3 Series UPS section for UPS without
the integrated PDU and remote control.
Overall, the PowerStation line is uniquely qualified for critical shipboard, vehicle,
airborne or land based systems combining advanced modular design features with highly
reliable construction
Technical Specifications: ETI0001-1429
AC OUTPUT |
Output voltage: |
120 VAC true sinewave standard,
others optional |
Output rating: UPS |
2400 in 3U chassis
0.65-0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: |
Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
Output frequency: UPS |
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available
0 or 0 Hz
available |
Operational status |
Status, load and battery level LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT |
Input voltage selection: |
Nominal 115 VAC, optional
autoranging input of 85-270 VAC |
Input voltage tolerance: UPS |
85-135 VAC @ full load without
using battery, to 70 VAC @ 75% load |
Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
Input/output isolation: |
Up to 3000 , up to 120 dB common mode,
<5 mA leakage |
Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
Input control/protection: |
Guarded 2 pole input breaker w/ UPS fuse
Optional cold start to turn on w/o AC present |
Input power connection: |
AMP CPC Type XII locking, various options |
BATTERY |
Battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
Battery life: |
Rated for continuous service life of 5 years |
DC protection: |
Panel mounted fuse, optional breaker |
Battery expansion: |
Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL |
Output circuits: |
Six controlled outputs via solidstate relays |
Output control: |
Local/remote control panel w/rocker switches
Thermal and remote interlock ON/OFF control |
Output receptacles: |
IEC320-15R w/cord restraints, various options |
MECHANICAL |
Dimensions ( H x D x W ): |
5.25 (3U) x 23.5 x 19.0 in (133
x 597 x 483 mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices patterns
standard, others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: |
115 lb. (52 kg) with lift handles front and rear |
Audible noise: |
Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: |
High capacity, positive pressure, forced air |
Cooling air direction: |
Rear intake, exhaust to front or sides or both |
Air intake filter: |
Washable filter media, various porosities |
ENVIRONMENTAL |
Storage temperature: |
-40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: |
32° to 113° F ambient (0° to 45° C
), lower/higher optional |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m) |
Operating elevation: |
Up to 15,000 ft (4,572 m), higher optionally |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D, 1399-300A, & 2000
|
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC Part 15, Class A
standard; MIL STD
461 optional |
OPTIONAL ACCESSORIES |
|
Autoranging International Input,
Emergency Power Off, Elapsed Time Meter, Cold Start, Alternate I/O Configurations,
Dual Source Input, Battery Expansion, Batteryless
Operation, Battery Charger/Conditioner, Power
Distribution Units, Software Interface,
Asynchronous serial COM port, 10BaseT
Ethernet SNMP/HTTP port, Transport Cases,
Slides and Mounting Kits |
:
November 23, 2011
|